5.3. Server Side Map Descriptors
5.3.1. FieldServer Specific Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name
Name of this Map
Descriptor
Up to 32 alphanumeric
characters
Data_Array_Name
Name of Data Array where
data is to be stored in the
FieldServer
One of the Data Array
names from “Data Array”
section above
Data_Array_Offset
Starting location in Data
Array
0 to maximum specified in
“Data Array” section above
Function
Function of Server Map
Descriptor
Server
Server_Hold_Timeout*
Specifies time FieldServer
will reserve Server side
connection while waiting for
the Client side to update
data in Data_Array (if
necessary)
>1.0s
5.3.2. Driver Specific Map Descriptor Parameters
Column Title Function Legal Values
Node_Name
Name of Node to fetch data
from
One of the node names
specified in “Client Node
Descriptor” above
Data_Type
This commonly used
parameter has no special
meaning to this driver and
may be omitted.
Register, Coil, AI, DI
Length Length of Map Descriptor 1 - 1000
Address
This commonly used parameter has no special meaning to
this driver and may be omitted.